Instant detection of wired connection loss, short circuits, and malfunctions
when 2EOL/3EOL connection is used
Depends on the connection type.
Power supply
Main
100–240 V~
Backup
12 V⎓, up to 7 Ah capacity with a full charge cycle of up to 30 hours
Type
type A
Used inside the protected premises.
Operating AC voltage range
100–240 V~, 50/60 Hz
Main power supply.
Operating DC voltage range
10.5–15 V⎓
Backup power supply.
Quiescent current consumption at nominal voltage
25 mA*
Maximum current consumption at nominal voltage
30 mA*
* From the backup rechargeable battery after the loss of the main power supply.
Backup rechargeable battery capacity
up to 7 Ah with a full charge cycle of up to 30 hours**
When a 4 Ah rechargeable battery is used, the minimum operating time at a maximum load of 1.7 А is 2 hours. For autonomous operation for 12 or 24 hours, the maximum load should not exceed 0.3 A and 0.15 A, respectively.
When a 7 Ah rechargeable battery is used, the minimum operating time at a maximum load of 1.7 А is 4 hours. For autonomous operation for 12 or 24 hours, the maximum load should not exceed 0.4 A and 0.2 A, respectively.
** It is the maximum time to recharge a 7 Ah battery to 80% of its capacity.
Power supply of connected wired devices
10.5–15 V⎓, up to 1 A (total maximum current consumption)
Three power supply lines from MultiTransmitter Fibra.
Power supply of connected fire detectors
10.5–15 V⎓, up to 0.4 A
One power supply line from MultiTransmitter Fibra.
Low battery voltage
11.6 V⎓
Low battery recovery voltage
12.9 V⎓
End-of-life battery voltage
11 V⎓
Maximum output peak-to-peak ripple battery voltage
200 mV⎓
Minimum backup rechargeable battery energy level in the charged state
100%
Casing
Dimensions
7.56″ × 9.37″ × 3.94″
Weight of the device in a black casing
28.04 oz
Excluding the backup rechargeable battery.
Weight of the device in a white casing
30.58 oz
Excluding the backup rechargeable battery.
Operating temperature range
from 14°F to 104°F
Operating humidity
up to 75%
Protection class
IP30, IK06
The new casing version of MultiTransmitter Fibra has light guides for the integration module LED indication, while the previous version has the LED indicator on the board.