FireProtect 2 (Heat/Smoke/CO) Jeweller user manual

Updated

FireProtect 2 (Heat/Smoke/CO) Jeweller user manual

FireProtect 2 (Heat/Smoke/CO) Jeweller is a wireless fire detector with a built-in siren. Designed for indoor installation. Detects smoke, temperature rise, and dangerous CO (carbon monoxide) level. The detector also can work without a hub.

There are two available modifications: one with sealed batteries (has SB in the name) that run for 10 years, and another with replaceable batteries (has RB in the name) that run for up to 5 years.

The detector operates as part of the Ajax system, communicating with the hub via the Jeweller secure radio protocol. The hub communication range is up to 5,577 ft without obstacles.

Functional elements

  1. The front panel of the detector with a Test/Mute button. To activate the button, press the center of the panel.

  2. SmartBracket mounting panel. To remove the panel, turn it counterclockwise.

  3. Device QR code and ID (serial number). It is used to add the detector to the Ajax system.

  4. Tamper button. Triggers when an attempt is made to detach the detector from the surface or remove it from the mounting panel.

  5. Detector certification information.

  6. Service button.

  7. First thermistor. Detects dangerous temperatures.

  8. Green LED indicator.

  9. Yellow LED indicator.

  10. Red LED indicator.

  11. Siren.

  12. Second thermistor. Detects dangerous temperatures.

  13. Information about the detector’s end of life date.

  14. Smoke chamber lid.

Operating principle

FireProtect 2 (Heat/Smoke/CO) is a wireless fire detector designed for indoor installation. Available in two versions:

  • The version with sealed batteries (the detector has SB in its name) ensures 10 years of autonomous operation. Once the batteries are discharged, replace the detector with a new one.

  • The version with replaceable batteries (the detector has RB in its name) ensures 5 years of autonomous operation. When the batteries are discharged, replace them with new ones.

How to replace FireProtect 2 RB (Heat/Smoke/CO) Jeweller batteries

The detector is equipped with a siren (piezoelectric buzzer) for audible notification of alarms and events with a volume of up to 85 dB (at a distance of 10 ft from the detector). The detector is always actives and reacts to a fire 24/7, regardless of the system’s security mode.

A smoke/temperature rise alarm can be easily distinguished from a high CO level alarm due to different audible and LED indications. Learn more about the types of indication of the detector’s alarms and events in the LED Indication section of this manual.

FireProtect 2 is protected by two tampers. The first tamper controls the removal of the detector from the SmartBracket mounting panel: the detector reacts with LED indication and sends notifications to users in Ajax apps and the security company monitoring station. The second tamper signals the removal of the smoke chamber lid, which is located under the front panel of the detector.

Ajax automation devices respond to FireProtect 2 alarms and perform user-defined actions using automation scenarios. For example, the WallSwitch relay can turn off the ventilation system and turn on emergency lighting when an alarm occurs.

Smoke sensor

FireProtect 2 detects smoke with a dual-spectrum optical sensor. Inside the smoke chamber, the sensor has blue and infrared LEDs that emit light at different wavelengths. This technology enables the detector to determine the size of volatile particles inside the chamber and respond to smoke.

The smoke chamber in FireProtect 2 is protected from dust, dirt, and insects. Even if dust gets inside and settles, this does not threaten or impair fire detection. The optical system is designed to prevent non-volatile particles from getting within the field of both blue and infrared LEDs at the same time. So that situation does not cause a false alarm.

The HazeFlow 2 software algorithm also protects against false alarms. When an alarm is detected, the algorithm additionally processes the data received from the detector and confirms the alarm.

Heat sensor

Inside FireProtect 2, there are two built-in thermistors that detect temperatures exceeding the threshold. These thermistors notify of alarms when a static temperature in the range of 135 °F (+58 °C) to 174 °F (+79 °C) is detected.

FireProtect 2 reports a temperature exceeding the threshold as soon as its value surpasses 135 °F (+58 °C).

CO (carbon monoxide) sensor

FireProtect 2 has a chemical sensor which detects dangerous levels of carbon monoxide. The operation principle of the sensor is based on a chemical reaction. There is an electrolyte bath inside the sensor. When a specific level of carbon monoxide is reached, a chemical reaction is triggered. The detector reads this event and transforms it into an alarm.

The detector raises an alarm if the CO level reaches:

  • 70 ppm (0.007%) — in 60–240 minutes.

  • 150 ppm (0.015%) — in 10–50 minutes.

  • 400 ppm (0.04%) — in 4–15 minutes.

A CO concentration of 400 ppm (0.04%) for three hours is life-threatening. The detector stops warning of a dangerous carbon monoxide level as soon as the concentration drops to 40 ppm (0.004%).

Test/Mute button

Тo activate the Test/Mute button, press lightly on the centre of the front panel with your hand. Use a suitable item (mop handle) if you can’t reach up the detector with your hand. Test/Mute is a mechanical button placed under the front panel of the detector.

The button performs several functions:

  • In normal mode, it starts the detector self-test.

  • In case of an alarm, it mutes the detector alarm or Interconnected Alarm of all fire detectors in the system for 5 minutes.

  • In case of a fault or a low battery level, it mutes the sound and LED indication for 12 hours.

  • In case of an end of life, it mutes the sound and LED indication for 29 days. After that, the indication can’t be muted.

Interconnected Fire Detectors Alarm*

All fire detectors of the FireProtect 2 product line support the Interconnected Alarm function. This function activates the built-in sirens of all fire detectors in the system as soon as at least one of the fire detectors detects an alarm. Sirens of FireProtect 2 detectors are activated within 20 seconds after an alarm is detected. FireProtect and FireProtect Plus are activated over a detector ping interval set in the Jeweller or Jeweller/Fibra settings, but no later than in 60 seconds.

The FireProtect 2 detectors have different sound and LED indications of alarm types to make it easier for users to distinguish between them. In case of interconnected alarm, all FireProtect 2 detectors indicate exactly the alarm type detected by the initiating detector.

How to set Interconnected Fire Detectors Alarms

How to mute Interconnected Fire Detectors Alarms

* For UL-certified FireProtect 2 detectors, the Interconnected Fire Detectors Alarm feature works only with a hub.

Sending events to the monitoring station

The Ajax system can transmit events and alarms to the PRO Desktop monitoring app as well as the Central Monitoring Station (CMS) via SurGard (Contact ID), SIA DC-09 (ADM-CID), ADEMCO 685, and other protocols. The list of supported protocols is available here.

Which CMSs Ajax connects to

Addressability of Ajax devices allows you to send not only events but also the type of the device, the name, virtual room, and security group assigned to it to the PRO Desktop and to the CMS. The list of transmitted parameters may differ depending on the type of the CMS and the selected communication protocol.

Adding to the system

Before adding a device

  1. Install the Ajax app.

  2. Log in to your account or create a new one.

  3. Select a space or create a new one.

    What is a space

    How to create a space

  4. Add at least one virtual room.

  5. Add a compatible hub to the space. Ensure the hub is switched on and has internet access via Ethernet, Wi-Fi, and/or mobile network.

  6. Ensure the space is disarmed, and the hub is not starting an update by checking statuses in the Ajax app.

Types of accounts and their rights

To connect to the hub, the detector should be within the coverage area of the hub radio network. To operate via a radio signal range extender, first connect the detector to the hub and then to the range extender. You can do this in the range extender settings in Ajax apps.

How to connect FireProtect 2 to a hub

  1. Open the Ajax app.

  2. Select the hub if you have several of them or if you are using the Ajax PRO app.

  3. Go to the Devices HubFilled-M tab. Press Add Device.

  4. Enter the name of the device.

  5. Scan the QR code or enter the ID manually. QR code is located on the rear part of the enclosure (under the mounting panel) and on the device packaging. The device ID can be found below the QR code.

  6. Select the virtual room and security group (if the group mode is enabled).

  7. Click Add; the countdown will begin.

  8. Turn on the detector by holding the service button for 3 seconds. The hub connection request is sent only if the detector is enabled. If the detector fails to connect to the hub, try again in 5 seconds.

Once connected, FireProtect 2 will appear in the hub device list in the Ajax app. Device status update depends on the ping interval set in the Jeweller or Jeweller/Fibra settings. The default value is 36 seconds.

FireProtect 2 only works with one hub. When connected to a new hub, the detector stops transmitting data to the old hub. Once added to a new hub, FireProtect 2 is not removed from the list of devices of the old hub. This must be done manually in Ajax apps.

Autonomous operation mode

FireProtect 2 detectors can be used autonomously without connecting to an Ajax hub. In this case, the detector notifies of fire, smoke, or dangerous CO level with only a built-in siren and LED indication. Users don’t receive notifications on any Ajax apps, including Ajax Translator, or PRO Desktop.

To use the detector autonomously, follow these steps:

  1. Select the optimal location of the detector using the recommendations in the Selection of installation place section.

  2. Mount the detector on the SmartBracket panel as described in the Installation section.

  3. Press the service button to switch on the detector.

  4. Wait at least 3 minutes and start a self-test with the Test/Mute button. Press the centre of the front panel and hold it for 1.5 seconds.

During a self-test FireProtect 2 notifies about each step with a built-in siren and LED indication. Once a self-test is completed, the LED indication turns off, and the detector works autonomously.

In case of an alarm, press the Test/Mute button or eliminate the cause of the alarm to mute the siren.

Indication

LEDs and the built-in siren of the detector can report alarms as well as certain states of the detector.

LED indication

Sound indication

Event

Notes

The red LED flashes 3 times every 1.5 seconds.

The siren sounds in time with the LED indication.

Alarm by:

  • smoke;

  • temperature threshold exceeded.

The detector stops alarming as soon as its sources are eliminated.

Also, you can mute the alarm by pressing the Test/Mute button or Button Jeweller, or using Ajax keypads. The alarm cannot be muted if there is a critical level of smoke in the air.

The LED and sound indications resume if the source of the alarm is still present after the muting timer (5 minutes) has expired.

The red LED flashes 4 times every 5 seconds.

The siren beeps in time with the LED indication.

Alarm by dangerous CO (carbon monoxide) level.

The detector stops alarming as soon as the CO level drops below 70 ppm.

You can also mute the alarm by pressing the Test/Mute button or Button Jeweller, or using Ajax keypads.

The LED and sound indications resume if the source of the alarm is still present after the muting timer (5 minutes) has expired.

No.

Short, low tone beep.

Prohibition on alarm muting.

The sound is played after pressing the Test/Mute button.

The alarm cannot be muted if there is a critical level of smoke in the air.

The red LED flashes every 4 seconds.

No.

Muted alarm.

The detector stops alarming as soon as its source is eliminated.

The red LED flashes 2 times in a row.

No.

Restore after alarm.

If the source of the alarm is removed, the detector is restored automatically.

The yellow LED lights up for 1 second.

No.

Tamper alarm.

The detector is removed from the SmartBracket mounting panel.

The green LED lights up for 1 second.

No.

The detector is installed on the SmartBracket mounting panel.

Turns on when the tamper is triggered.

Green, yellow, and red LEDs light up in turn, then go off.

No.

Turning the detector on.

To turn on the detector, hold the service button for 1 second.

Green, yellow, and red LEDs light up at the same time, then go off in reverse order.

No.

Turning the detector off.

To turn off the detector, hold the service button for 2 seconds.

The green LED is permanently on.

No.

Connection to the hub in progress.

The indication turns off after the detector is connected to the hub.

The green LED flashes 6 times in a row.

No.

The detector has been removed from the hub.

The indication turns on when the detector receives information that it has been removed from the hub.

The yellow LED flashes 2 times in a row every minute.

The siren beeps in time with the LED indication every minute.

Malfunction detected.

All malfunctions are displayed in the detector states in Ajax apps. Fields with malfunctions are highlighted in red.

If the detector needs to be repaired, contact our Technical Support.

The yellow LED flashes once per minute.

The siren beeps in time with the LED indication once per minute.

Low battery level.

You can replace batteries in a detector with replaceable batteries only (has RB in its name). A detector with sealed batteries (with SB in the name) should be replaced with a new one after the batteries are discharged.

How to replace batteries in FireProtect 2 RB (Heat/Smoke/CO)

The yellow LED constantly flashes.

No.

The battery is completely discharged.

You can replace batteries in a detector with replaceable batteries only (has RB in its name). A detector with sealed batteries (with SB in the name) should be replaced with a new one after the batteries are discharged.

How to replace batteries in FireProtect 2 RB (Heat/Smoke/CO)

The red LED flashes 5 times during the smoke chamber test. Then flashes 3 more times but slower during the CO sensor test.

The siren beeps 5 times during the smoke chamber test. Then it makes 3 longer beeps during the CO sensor test.

Performing a self-test.

The test can be started by pressing the Test/Mute button or in the detector settings in the Ajax app.

In CO-free versions, only the smoke chamber is tested.

The yellow LED flashes 3 times in a row every minute.

The siren beeps 3 times every minute.

The device service life has expired.

The device has operated for more than 10 years. The sensitivity of its sensors may have decreased.

We recommend replacing this detector with a new one.

Detector testing

Functionality testing

The test allows you to check the status of the detector’s sensors. You can run it in two ways: by pressing the Test/Mute button of the detector and in Ajax apps.

To run the test using the Test/Mute button, press the center of the front panel and hold it for 1.5 seconds.

To run the test in the Ajax app:

  1. Open the Ajax app.

  2. Select the hub if you have several of them or if you are using the Ajax PRO app.

  3. Go to the Devices HubFilled-M menu.

  4. Select FireProtect 2 (Heat/Smoke/CO).

  5. Go to the settings by clicking on the gear icon Settings-M.

  6. Click on the Self-test field.

After starting the test, the red LED of the detector blinks 5 times in a row and then blinks 3 more times but slower. The detector’s siren sound in time with an LED indication. When the test is over, users receive a notification about the detector state in Ajax apps.

The detector also notifies about the test result with sound and LED indications. If the test is failed and a malfunction is detected, the detector starts to Indicate a malfunction 3 seconds after the test is begun: the yellow LED blinks twice, and the siren beeps in time with the LED indication.

Testing at the place of installation

Ajax system provides several tests to select the correct installation place of devices. Jeweller Signal Strength Test is available for FireProtect 2. The test determines the strength and stability of the signal at the intended location of the device.

To run the test in the Ajax app:

  1. Select the hub if you have several of them or if you are using the Ajax PRO app.

  2. Go to the Devices HubFilled-M menu.

  3. Select FireProtect 2 (Heat/Smoke/CO).

  4. Go to the settings by clicking on the gear icon Settings-M.

  5. Select Jeweller Signal Strength Test.

  6. Perform the test following the tips in the app.

Icons

The icons show some of the device states. You can view them in Ajax apps in the Devices HubFilled-M tab.

Icon

Meaning

SignalStrength3-S

Jeweller signal strength between the detector and the hub or radio signal range extender. The recommended value is two or three bars.

Learn more

Battery80-S

Battery charge level of the device.

Learn more

Chain-S

The Interconnected Fire Detectors Alarm feature is activated.

Learn more

AlwaysActive-S

The detector operates in the Always Active mode.

The icon is displayed permanently. FireProtect 2 is always active and responds to a fire 24/7, regardless of the system’s security mode.

Learn more

RexConnected-M

The detector operates through the radio signal range extender.

TemporaryDeactivationWholeDevice-S-red

The detector is deactivated.

Learn more

Temperature-M

The detector has detected that the temperature threshold has been exceeded.

SmokeDetected-M

The detector has detected smoke.

COLevel-M

The detector has detected the dangerous CO (carbon monoxide) level.

Lid-S

The detector was removed from the SmartBracket mounting panel, or the enclosure integrity was violated in another way. Check the mounting of the detector.

Volume-S

The detector’s siren plays an alarm sound.

Uptime-S

The detector service life has expired.

The device has been operated for more than 10 years. The sensitivity of its sensors may have decreased. We recommend replacing this detector with a new one.

Warning-S

Malfunction detected. The list of malfunctions is available in the detector states.

TemporaryDeactivationTamperRed-M

The detector has tamper triggering events deactivated.

Learn more

offline

The device has lost connection with the hub or the hub has lost connection with the Ajax Cloud server.

not-transferred

The device has not been transferred to the new hub.

Learn more

States

The states include information about the device and its operating parameters. You can see FireProtect 2 (Heat/Smoke/CO) states in Ajax apps. To access them:

  1. Open the Ajax app.

  2. Select a hub if you have several of them or if you are using the Ajax PRO app.

  3. Go to the Devices HubFilled-M tab.

  4. Select the device from the list.

Ajax apps display two FireProtect 2 temperature parameters. The first one shows the air temperature in the room where the detector is installed. The second parameter, Temperature Threshold Exceeded, shows whether fire-related temperature changes are detected. This value may differ from the temperature in the room.

Parameter

Meaning

Data import

Displays the error when transferring data to the new hub:

  • Failed — the device has not been transferred to the new hub.

Learn more

Temperature

Air temperature in the room where FireProtect 2 is installed. Measured in Celsius or Fahrenheit degrees depending on the app settings.

In the normal state, the temperature value is displayed in black.

When the temperature rises, the field is highlighted with red.

Learn more

Jeweller Signal Strength

Jeweller signal strength between FireProtect 2 and the hub or radio signal range extender.

The recommended value is two or three bars.

Jeweller is a protocol for transmitting FireProtect 2 events and alarms.

Connection via Jeweller

Connection status between FireProtect 2 and the hub or range extender via Jeweller:

  • Online — the detector is connected to the hub or range extender. Normal state.

  • Offline — no connection between the detector and the hub or range extender. Check the detector connection.

Battery Сharge

The battery charge level of the device:

  • OK — detector batteries have sufficient charge. Normal state.

  • Battery low — detector batteries are discharged.

When the batteries are discharged, users and the security company monitoring station receive a notification.

After the low battery notification, the detector is able to operate for another month under normal conditions. In case of an alarm, the battery charge is enough to ensure 4 minutes of the sound and LED indication operation.

How the battery charge is displayed
Battery life calculator

You can replace batteries in a detector with replaceable batteries only (has RB in its name). A detector with sealed batteries (with SB in the name) should be replaced with a new one after the batteries are discharged.

How to replace batteries in FireProtect 2 RB (Heat/Smoke/CO)

Lid

The status of the detector’s tamper that responds to detachment of the device from the surface or opening of the enclosure:

  • Open — the detector is removed from the SmartBracket mounting panel, or the enclosure integrity is violated in another way. Check the mounting of the detector.

  • Closed — the detector is installed on the SmartBracket mounting panel. The integrity of the device enclosure and the mounting panel is not violated. Normal state.

Learn more

Smoke

Smoke sensor status:

  • Clear — normal state, the detector does not detect smoke.

  • Alarm — the detector detects smoke.

If smoke is detected, the text field highlights red.

Learn more

Temperature Threshold Exceeded

Alarm state if temperature threshold is exceeded:

  • No — normal state, the detector does not detect temperature threshold exceeding.

  • Alarm — the detector has detected temperature threshold exceeding.

If temperature threshold exceeding is detected, the text field highlights red.

Learn more

High CO Level

CO (carbon monoxide) level in the room where FireProtect 2 is installed:

  • No — the CO level is normal.

  • Alarm — the detector has detected a dangerous CO level.

If a dangerous CO level is detected by the detector, the text field will turn red.

Learn more

Permanent Deactivation

Shows the status of the device permanent deactivation function:

  • No — the device operates in normal mode.

  • Lid only — detector’s tamper triggering notifications are disabled.

  • Entirely — the detector does not execute system commands, does not participate in automation scenarios, and does not send notifications of alarms, malfunctions, and other events to the CMS and system users. In this case, the detector will continue to operate autonomously and indicate alarms using the built-in siren.

Learn more

Firmware

FireProtect 2 firmware version.

Device ID

ID (serial number) of FireProtect 2. Also available on the detector’s enclosure (under the mounting panel) below the QR code and on the packaging box.

Device No.

The number of FireProtect 2 loop (zone). Events are sent to the CMS with this number.

Settings

To change FireProtect 2 (Heat/Smoke/CO) settings in an Ajax app:

  1. Open the Ajax app.

  2. Select the hub if you have several of them or if you are using the Ajax PRO app.

  3. Go to the Devices HubFilled-M tab.

  4. Select the device from the list.

  5. Go to Settings by clicking on the gear icon Settings-M.

  6. Set the required settings.

  7. Click Back to save the new settings.

Settings

Meaning

Name

Detector name. Displayed in the list of hub devices, text of SMS and notifications in the events feed.

To change the name, click on the text field.

The name can contain up to 12 Cyrillic characters or up to 24 Latin characters.

Room

Selecting the virtual room to which FireProtect 2 is assigned.

The room name is displayed in the SMS text and notifications in the events feed.

To change the room, click on the field.

Alert with a siren

If temperature threshold exceeded

When this option is enabled, the Ajax sirens connected to the system are activated when the detector detects a temperature threshold exceeding.

If smoke detected

When this option is enabled, Ajax sirens connected to the system are activated when the detector detects smoke.

If CO detected

When this option is enabled, the Ajax sirens connected to the system are activated when the detector registers a dangerous CO level.

Jeweller Signal Strength Test

Switches the detector to the Jeweller signal strength test mode. The test helps determine the optimal place for installing FireProtect 2.

The test shows the signal strength between the detector and the hub or range extender via the Jeweller wireless data transfer protocol.

The recommended value is two or three bars.

Learn more

Smoke Sensor Self-test

Runs a detector self-test.

Learn more

User Guide

Opens FireProtect 2 User Manual in the Ajax app.

Permanent Deactivation

Allows to deactivate the device without removing it from the system. Three options are available:

  • No — the device operates in normal mode.

  • Lid only — detector’s tamper triggering notifications are disabled.

  • Entirely — the detector does not execute system commands, does not participate in automation scenarios, and does not send notifications of alarms, malfunctions, and other events to the CMS and system users. In this case, the detector will continue to operate autonomously and indicate alarms using the built-in siren.

Learn more

Unpair Device

Unpairs FireProtect 2 from the hub and deletes its settings.

Battery life optimization setting

The Battery Life Optimization feature is provided to save the detectors’ battery charge. It is available only for hubs on OS Malevich 2.14 or higher with FireProtect 2 detectors connected. This feature is enabled by default.

When the Battery Life Optimization feature is enabled, the hub increases the ping interval for FireProtect 2 detectors.

To disable the Battery Life Optimization feature:

  1. Open the Ajax app.

  2. Select the hub with FireProtect 2 detectors connected.

  3. Go to:HubSettings Settings-MServiceFire Detectors Settings.

  4. Disable the Battery Life Optimization toggle.

  5. Click Back to save the settings.

Selection of installation place

The coverage area of one FireProtect 2 (Heat/Smoke/CO) is 538–646 sq. ft, depending on the type of premises.

The detector should be installed in every room. The detector is placed in the center of the ceiling at a distance of 12″ from light fixtures, chandeliers, or any other decorative objects that may interfere with alarm detection.

If there are beams on the ceiling protruding 12″, depending on the type of premises.

or more, the detector must be installed between every two beams. If the beams protrude by less than 12″, installation on a beam in the central part of the ceiling is allowed.

In halls or narrow corridors, detectors should be installed at a distance of no more than 24.6 ft from each other.

If the ceiling is sloping, the detector is installed at a distance of 23.6″ from the top point of the ceiling. To select an installation place, draw a straight line down from the top of the ceiling. Then, draw a perpendicular from this line to the sloping part of the ceiling. The detector is installed at this point.

ajax fireprotect

We do not recommend mounting the detector on a wall. This installation is acceptable if closely spaced beams or other obstacles interfere with the installation of the detector. Wall mounting is possible only if the detector is placed at a distance of 6–12″ below the ceiling but above the doorways.

When choosing the location of the detector, consider the parameters that affect its operation:

  • Jeweller signal strength.

  • Distance between the detector and the hub.

  • Presence of barriers for radio signal passage between devices: walls, interfloor ceilings, large objects located in the room.

Consider the placement recommendations when designing your Ajax system for the object. The security system must be designed and installed by specialists. The list of recommended Ajax partners is available here.

Signal strength

The Jeweller signal strength is determined by the ratio of the number of undelivered/corrupted data packets that are exchanged between the hub and the detector to expected ones within a certain period of time. Signal strength is indicated by the icon SignalStrength-M on the Devices HubFilled-M tab:

  • Three bars — excellent signal strength.

  • Two bars — good signal strength.

  • One bar — low signal strength; stable operation is not guaranteed.

  • Crossed out icon — no signal; stable operation is not guaranteed.

Check the Jeweller signal strength at the installation site. If the signal strength is as low as one or zero bars, we cannot guarantee stable operation of the device. In this case, move the device. Repositioning even by 8 inches can significantly improve the signal reception.

If, after relocation, the detector still has a low or unstable signal strength, use a radio signal range extender.

Do not install the detector

  • Outdoors. This can lead to the detector failure.

  • In places with low or unstable Jeweller signal strength. This can result the connection loss.

  • Inside premises with temperature and humidity outside the permissible limits. This could damage the detector.

  • In places with fast air circulation. For example, near fans, vents, open windows, or doors. This may interfere with Smoke/Heat and CO detection.

  • Opposite any objects with rapidly changing temperature. For example, electric and gas heaters. This can lead to false alarms.

  • In the corners of the room. This may interfere with fire detection.

  • In bathrooms, showers, or other areas where the temperature changes rapidly. This can lead to false alarms.

  • In rooms where the generation of gases/vapors/smoke is part of the operating process. For example, in a garage, where the possibility of a detector’s alarm due to vehicle exhaust gases exists. For such premises we recommend using a detector without a smoke sensor: FireProtect 2 (Heat/CO).

  • In very dusty places or areas with a lot of insects. Insects, dust, and other contaminants can settle on the smoke chamber lid and prevent fire detection.

  • Near lighting fixtures, decorations, and other interior items that may interfere with the circulation of air in the room. This may interfere with fire detection.

  • On surfaces that are usually warmer or colder than the rest of the room. For example, roof traps. Temperature fluctuations can interfere with fire detection.

  • In high or inconvenient places. Access to the Test/Mute button is required to mute the alarm and test the detector if it’s used without connection to a hub.

Installation

To install the detector:

  1. Remove the SmartBracket mounting panel from the detector. To remove the panel, turn it counterclockwise.

  2. Fix the SmartBracket panel to a surface using double-sided adhesive tape or other temporary fasteners. The mounting panel has an UP sign, which indicates the correct position.

  3. Run the Jeweller signal strength test. The recommended value is two or three bars.

    If the signal strength is a single bar or lower, we cannot guarantee the stable operation of the detector. Consider to relocate the device as repositioning even by 8 inches can significantly improve the signal strength. If there is still low or unstable signal after the relocation, use a radio signal range extender.

  4. Remove the detector from the mounting panel.

  5. Attach the SmartBracket panel with the bundled screws using all fixation points. When using other fasteners, make sure they do not damage or deform the mounting panel.

  6. Place the detector on the SmartBracket mounting panel.

  7. Adjust the position of the detector if necessary.

Actions to take in case of Fire alarm (Smoke/Heat)

  1. Don’t open the doors if you feel heat or smoke behind them. Check other entries and use an alternative way to escape. Close all doors behind you as you leave.

  2. Evacuate as quickly as you can, don’t panic. Save time, and don’t pack your things. Arrange a meeting place outside for everybody in the building. Check if everyone got out safely.

  3. Call the fire department immediately by yourself or ask someone nearby. Remember, even the smallest fire can spread quickly, so do not hesitate to call the fire department. Call the fire department even if the alarm is automatically transmitted to a monitoring station.

Actions to take in case of CO alarm

  1. Immediately open all the doors and windows to ventilate the premises if it is safe.

  2. Stop using and turn off all fuel devices where it is possible.

  3. Evacuate from the premises leaving the doors and windows open.

  4. If you have a headache and nausea, get medical help immediately. These could be the result of carbon monoxide poisoning, so tell your doctor about it.

  5. Call your gas or other fuel supplier’s hotline. Keep the number in a noticeable place.

  6. Avoid re-entering the premises until the alarm stops.

  7. Do not use the fuel or gas appliances again until registered installers or experts have checked them.

Carbon monoxide impact

Carbon monoxide poisoning occurs regularly: many people are killed each year, and many more suffer ill health. CO is an invisible, odorless, tasteless, and extremely toxic gas. CO is produced by burning such fuels as petrol, diesel, coal, oil, natural/bottled gas, paraffin, wood, charcoal, etc. The heart and brain are rapidly damaged by oxygen starvation because red blood cells in the lungs absorb CO faster than oxygen.

The most common reasons for high levels of CO in premises:

  • Engines of cars, generators, etc., are left running in confined spaces (for example, a garage).

  • Incorrectly or poorly installed fuel-burning appliances.

  • Blocked or damaged vents or chimneys/flues.

  • The tightness of rooms where appliances for burning fuel or fireplaces are installed.

  • Bad ventilation in rooms with portable gas/paraffin heaters.

The CO exposure period is also important. A low level for a long period (e.g., 150 ppm for 90 minutes) can cause the same symptoms as a high level of CO for a short period (e.g., 300 ppm CO for 30 minutes). The table below shows how different concentrations of CO affect people.

CO concentration in the air, ppm

Approximate inhalation time and consequences

35

The maximum allowable concentration for continuous exposure in any 8-hour period (according to Occupational Safety and Health Association; OSHA).

150

Slight headache after 1.5 hours.

200

Slight headache, fatigue, dizziness, and nausea after 2–3 hours.

400

Frontal headaches within 1–2 hours, life-threatening after 3 hours.

800

Dizziness, nausea, and convulsions within 45 minutes. Unconsciousness within 2 hours. Death within 2–3 hours.

1,600

Headache, dizziness, and nausea within 20 minutes. Death within 1 hour.

3,200

Headache, dizziness, and nausea within 5–10 minutes. Death within 25-30 minutes.

6,400

Headache, dizziness, and nausea within 1–2 minutes. Death within 10–15 minutes.

12,800

Death within 1–3 minutes.

Malfunctions

ajax fireprotect

If FireProtect 2 malfunction is detected (for example, there is no connection with the hub), the malfunction counter is displayed in the device field in the Ajax apps.

All malfunctions are displayed in the detector States. Fields with malfunctions are highlighted in red.

The device can report malfunctions to the CMS, as well as to users through push notifications and SMS.

FireProtect 2 (Heat/Smoke/CO) malfunctions

  • No connection with the hub or radio signal range extender.

  • The detector’s enclosure is open.

  • Low battery charge level.

  • The device service life has expired.

  • Hardware malfunction (failure of one or more sensors of the detector).

Maintenance

The detector has a self-test system and does not require the user or installer intervention. The smoke chamber is protected from dust and insects, so there is no need to clean it. We recommend to periodically run a self-test to familiarize people with the alarm sound and LED indication.

Clean the detector enclosure of dust, cobwebs, and other contaminants as they emerge. Use a soft dry cloth suitable for equipment care. Do not use substances that contain alcohol, acetone, gasoline, and other active solvents to clean the device.

The service life of the detector is 10 years. After this period, the sensitivity of the sensors decreases. We recommend replacing the detector with a new one to ensure uninterrupted fire protection at the premises.

The version of the detector with replaceable batteries (has RB in the name) operates from pre-installed batteries for up to 5 years. When the batteries are discharged, replace them with new ones.

How to replace batteries in FireProtect 2 RB (Heat/Smoke/CO)

A detector with sealed batteries (has SB in the name) should be replaced with a new one after the batteries are discharged.

Buy FireProtect 2 (Heat/Smoke/CO)

Cautions

Situations that must be avoided

Situation

Possible consequences

Contamination by alkaline metals

Significant changes to the sensor characteristics when the sensor is contaminated by alkaline metals, especially salt water spray.

Exposure to high concentrations of common (non-acidic) gases

Exposure to high concentrations of common gases such as ammonia may cause irreversible changes. Avoid long-term exposure to or use of packing materials that may generate common gases.

Impact of volatile organic compounds (VOCs)

Prolonged off-gassing from such VOCs may cause irreversible changes to:

  • styrene (commonly used in blister packs and packing trays);

  • α-pinene (found in some kinds of printing inks).

Avoid packing the FireProtect 2 in a tightly closed container where VOC gases may be present.

Excessive exposure to alcohol or acetone vapors the sensor may cause its temporary disability.

Contact with water

Soaking or splashing the sensor with water may change its characteristics.

Situations to avoid whenever possible

Situation

Possible consequences

Exposure to silicone vapors

Sensor failure because of the exposure to silicone adhesives, hair grooming materials, or silicone rubber/putty.

Dew condensation

The clog of gas diffusion route or deterioration of the sensing membrane. Avoid severe dew condensation that occurs for an extended period inside or on the sensor surface.

Exposure to hydrogen sulfide or sulfuric acid gas

Sensor components corrosion, resulting in sensor damage.

Presence of dust and oil mist

Clogging of the sensor’s internal structure caused by extremely high dust or oil mist concentrations.

Additional cautions for installation

Technical specifications

All technical specifications of FireProtect 2 RB (Heat/Smoke/CO) UL Jeweller

All technical specifications of FireProtect 2 SB (Heat/Smoke/CO)

Compliance with standards

Warranty

Warranty for the Limited Liability Company “Ajax Systems Manufacturing” products is valid for 2 years after the purchase.

If the device does not function correctly, please contact the Ajax Technical Support first. In most cases, technical issues can be resolved remotely.

Warranty obligations

User Agreement

Contact Technical Support